Klargester Envirosafe

The Klargester Envirosafe has been designed to cater for the current effluent standards and the more stringent standards likely to be demanded in the future.

We are seeing tighter NH3  consent standards being set by the Environment Agency, and the Klargester Envirosafe is adaptable at the build stage to suit many different requirements.

FeaturesKlargester Envirosafe image

  • High performance 
  • Adaptable to specific consent requirements including ‘Total Nitrogen’
  • Small footprint area
  • Single piece tank for rapid installation and reduced costs
  • Variable invert options
  • Low visual impact, (below ground)
  • Low running costs
  • May be installed in under driveway areas
  • Compliant with EN-12255 - Tank Strength
  • Designed for applications selected in compliance with British Water Code of Practice Flows and Loads
  • Low maintenance
  • Alarm protected

Process Described

Envirosafe sewage treatment plants employ a combination of aerobic and anerobic processes in a fluidised bed arrangement. This operates in conjunction with an advanced system of air diffusers and selected media to klargester Envirosafe switchboard.deliver optimum levels of purification.

This process takes place in three distinct stages:-

  1. Primary Settlement
    This is the initial stage of treatment and simply involves the settlement of larger solids present in raw sewage and wastewater for subsequent gradual breakdown. Envirosafe features two chambers to ensure efficient operation with a flow balancing facility. 
  2. Biological Treatment
    Substantial BOD reduction takes place here, where the carbonaceous pollutants are removed by presenting the sewage to the micro-organisms in the presence of oxygen.
    The treatment is achieved by high efficiency air diffusers continually pumping oxygen through the biological media'. Standard Envirosafe models utilise two aerobic treatment chambers for lower performance applications. Where higher effluent standards are required, the plant employs a third anerobic zone.
  3. Settlement
    A natural by-product of biological treatment is humus sludge and this is separated for further treatment. The treated effluent is discharged via the outlet. In standard configuration Envirosafe will deliver a treatment better than 20mg/l BOD, 30mg/l S.S., with ammonia levels better than 5mg/l depending on the application. Total nitrogen consents can be achieved with this plant (contact WTE for your application).

Flow Management

Envirosafe’s design incorporates flow management in order to avoid volume variations and to minimize flow impact on the final settlement process.  Flow management ensures that final effluent quality remains consistently high.

Options

  • Choice of inverts (from 0.5 to 2.0m)
  • Duty and Standby blowers (as required)
  • Alarm Systems
  • Pumping stations
  • Extension shafts (to 2.0m maximum standard invert) 
  • Separate sample chambers for accurate and convenient effluent sampling, as required by the relevant authorities.

WTE offer a full Installation service. Please visit our Installation section for more information.

WTE offer a full after sales service involving scheduled maintenance visits.

Envirosafe Technical Specifications

Klargester envirosafe c/s

Model 34000 38000 42000 47000 55000 67000 80000
A Overall Length (m) 7.4 8.2 9.0 9.7 11.2 13.5 15.8
B Overall Width (m) 2.8 2.8 2.8 2.8 2.8 2.8 2.8
C Height (m)              
560mm Inlet / 860mm Outlet Invert* 2.9 2.9 2.9 2.9 2.9 2.9 2.9
1060mm Inlet / 1360mm Outlet Invert* 3.4 3.4 3.4 3.4 3.4 3.4 3.4
1560mm Inlet / 1860mm Outlet Invert* 3.9 3.9 3.9 3.9 3.9 3.9 3.9
2060mm Inlet / 2360mm Outlet Invert* 4.4 4.4 4.4 4.4 4.4 4.4 4.4
D Diameter (m) 2.6 2.6 2.6 2.6 2.6 2.6 2.6
Volume (m³) 34 38 42 47 55 67 80
Weight approx (kg) 3000 3200 3400 3800 4200 4700 5400
Inlet / Outlet Diameter (mm) 160 160 160 160 160 160 160
BOD 5ATU load (kg/day) 4.5 6 7.5 9 12 15 18
Ammonia (kg/day) 0.6 0.8 1.0 1.2 1.6 2.0 2.4
Maximum flow (m³/day) 15 20 25 30 40 50 60
Retention time (hrs) 33 29 29 33 29 29  

Notes:
* Extension turrets can be added to achieve deeper inverts, though this can limit access for maintenance. Alternative pipe sizes may be ordered.
Weights are for empty tanks.  All weights are approximate.
Kingspan Environmental reserve the right to alter the above dimensions without prior notice.

WTE are able to assist with the mandatory consent to discharge application from the Environment Agency or SEPA prior to installation.

All Klargester products have a full initial 12 month warranty covering all mechanical and electrical components against malfunction, provided the unit has not been subject to damage or abuse




Powered by Create

Installers Wanted
Installers wanted throughout UK and Ireland for all types of  treatment plant installations.
Tel 01757 288022
Latest News
Keep up to date with the latest news  on waste water issues.
 The British Standards Institute has told us that  the EN12566-3 2005 is the only current British Standard.
 
  BIOROCK
Achieves amazing 4:3:3 for its new EN test results!
Act on CO2
biorock sewerage treatment unit image
No Electricity
BIOROCK
 The system you have been waiting for!
Septic Tank Failure
Free surveys for soakaway failures.  Full reports  for Litigation
Caravan Parks
Valence  large wastewater systems are excellent value for money.
Wastewater Tutorial
Sewage treatment plant and septic tank system design and construction: